Walchem WebMaster Manuel d'instructions Page 61

  • Télécharger
  • Ajouter à mon manuel
  • Imprimer
  • Page
    / 180
  • Table des matières
  • DEPANNAGE
  • MARQUE LIVRES
  • Noté. / 5. Basé sur avis des utilisateurs
Vue de la page 60
57
The relay input assignment choices will be any digital or optional analog inputs that are defined as
a flow meter input.
If the relay control mode is any of the Biocide Timer Based Feed options:
The relay input assignment is Not Applicable.
If the relay control mode is Feed with Another Relay, Feed After Another Relay (%) or Feed After
Another Relay (Fixed Time):
The relay input assignment choices will be all the other relays.
If the relay control mode is Feed as % Time or Dispersant:
The relay input assignment is Not Applicable.
If the relay control mode is any of the Spike modes:
The relay input assignment choices will be all sensors and analog inputs.
If the relay control mode is Alarm:
The relay input assignment is Not Applicable.
If the relay control mode is Activate on a DI:
The relay input assignment will be any Interlock or Generic Input digital inputs.
Analog Output Input Assignment (1 – 4)
This section will only appear if there are one or more 4-20 mA output cards installed.
Use the pull-downs to select the input signal that will be retransmitted as a 4-20 mA output signal.
The possible choices include any sensor input, any sensor temperature signal, or any 4-20 mA
input signal (only applicable if the analog input card is installed).
LCD Display Setup
Up to five parameters may be presented on the front panel LCD display. Click on the radio buttons
next to the parameters to show.
6.3 System Summary Menu
There are no programmable parameters in the System Summary Menu page. Several tables will be
displayed, with information on sensor readings, analog input readings, digital input states, alarms,
relay state, etc.
Vue de la page 60
1 2 ... 56 57 58 59 60 61 62 63 64 65 66 ... 179 180

Commentaires sur ces manuels

Pas de commentaire