Power-up Alarm Delay Time
In order to avoid being notified of an alarm condition that is only present because the system is
just powering up, you set a delay time for the alarm action. If the alarm condition still exists at the
end of the delay time, then the alarm relay will activate. If the alarm condition no longer exists at
the end of the delay time, no notification will occur. Any value between 0 and 1440 minutes is
acceptable.
If this Relay is a Dry Contact
Use this section if the relay board installed in this controller has a dry contact relay in the position
of the relay being programmed as an alarm. If you look at the relay board, find the relay number
you are programming as the alarm, and if it has terminals labeled NC and COM, it is dry contact.
Click on the radio button that describes how you want the alarm relay to act. The normal method is
to close the relay when an alarm condition exists, but you can also open the relay.
If this Relay is Internally Powered
Use this section if the relay board installed in this controller has an internally powered relay in the
position of the relay being programmed as an alarm. If you look at the relay board, find the relay
number you are programming as the alarm, and if it has terminals labeled NC and NO, it is
internally powered.
Click on the radio button that describes how you want the alarm relay to act. The normal method is
to energize the NO (normally open) terminal when an alarm condition exists, but you can also
energize the NC (normally closed) terminal.
Mutual Interlocks
Click the check boxes to select or de-select the relays and analog output control outputs that you
want to be prevented from turning ON if this output relay is already ON. If you do not need any
other output to shut off when this relay turns on, UNCHECK all boxes. The selection is mutually
exclusive, meaning that if Relay 2 has Relay 4 interlocked, then R2 won’t turn on if R4 is already
on, and R4 won’t turn on if R2 is already on. This feature should be used with caution since it can
potentially delay a chemical addition for a long time.
Output Time Limit
Type in the text box the maximum amount of time that the relay can be continuously activated
before the controller deactivates the relay and activates an Output Time Limit alarm. This is
intended to prevent the output from running out of control if the input fails in such a way that it
will never deactivate the relay. Any value between 0 and 1440 is acceptable. A value of 0 means
the relay can be left on indefinitely.
Note that the relay will not activate again until someone resets the timer!
It will take some experience to find out what the normal output on-time will be. If the relay cycles
open and closed under worst case conditions in 30 minutes, you may want to set the Output Time
Limit at 60 minutes.
Output Mode
Click on the radio buttons to manually control the alarm relay. The normal selection will be Auto,
where the controller uses the various set points to open and close the relay. You can force the relay
open regardless of the presence of an alarm condition by selecting Off, or force the relay closed
regardless of the presence of an alarm condition by selecting Hand.